| Cable mark |
Cable leads quantity |
Nominal cut, mm |
|
1 — 4 5 |
1.0 — 240 1.0 — 120 |
Cable leads electric resistance, counted in 1 km of the cable length and temperature 20C , not less than 50 MOhm.
Main cable leads cuts till 4 mm inclusively, should be persistent to multiple bends through the roll system under the current load and carry not less than 30000 bends cycles.
Nominal roll diameter and load, which creates the cable drawing power, should correspond to the values, which are given in Table 1.
Main cable leads cuts 6.0 mm and more should be persistent to multiple bends for the corner ± π/2 radius having nominal stretching force 49H (5.0 kilogram-force).
Nominal roll diameter and cycles amount should correspond to the indicated values in Table 2.
Cable factory length with nominal lead cut till 35 mm inclusively 150 m not less, the cable with lead cut till 50 mm and more, not less than 125 m.
Protractedly allowed temperature of lead 70C.
Cables do not spread the combustion in bundle laying (category A).
Cable service life is not less than 4 years.
Warranty period of cable is 12 months since its break-in.
Table 1
| Main leads cuts |
Nominal rolls diameter, mm |
Nominal tensile load H (kilogram – force) |
| 1.5 |
120 |
10 (1.0) |
| 2.5 |
120 |
15 (1.5) |
| 4.0 |
160 |
25 (2.5) |
Table 2
| Main leads cuts |
Nominal rolls diameter, mm |
Nominal tensile load H (kilogram – force) |
| From 7 till 25 inclusively |
200 |
9000 |
| From 25 till 40 inclusively |
200 |
6000 |
| 40 |
400 |
4000 |